Nuestras marcas

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
How to upgrade your NMC2 & NMC3 firmware using the NMC Firmware Update Utility

Article available in these languages: Francés

Issue:
The customer asked how to upgrade the firmware through the utility tool.

Product line:
NMC2, NMC3

Environment:
AP9630, AP9631, AP9640 & AP9641

Cause:
Web interface displays a UPS "not recognized" error or the customer is installing a new NMC.

Resolution:
Please follow the next steps.
1. Access the Downloads page.

2. Locate firmware for the product by NMC model (ie AP9630).

(NOTE: Some products' firmware is not available on the download page. Contact Technical Support for support on products not found on the firmware download page.)

3. Run the application and enter the following information.

  1. Host (Ip address of the unit)
  2. UserName and Password of the NMC
  3. Click on Start Update

If you notice that the application stops with the selected protocol (SCP for this case) please try with FTP.
Firmware utility



Schneider Electric España

  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies