Why does my VVX ThinfinityVirtualUI service fail to start automatically after a reboot?
Always backup the registry before making any changes.*
After rebooting the machine, VVX doesn’t launch, and the ThinfinityVirtualUI service do not start automatically. What might be the cause, and how can it be resolved?
Please note that in older Geo SCADA releases, there maybe more than one service.
Services configured as "Automatic" have a default timeout period to start. If Windows is unable to attend the service during this time, the service doesn't start.
The key below will allow you to configure a higher timeout.
Go to Start > Run > and type regedit.
Navigate to: HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Control.
With the control folder selected, right click in the pane on the right and select new DWORD Value.
Name the new DWORD: ServicesPipeTimeout.
Right-click ServicesPipeTimeout, and then click Modify.
Click Decimal, enter the desired value in milliseconds. For example type '180000' for 3 minutes, and then click OK.
This setting will take effect on the next restart of the computer.
Publicado para: Schneider Electric España


¿Necesitas ayuda?
Selector de productos
Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.
Pedir presupuesto
Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.
Centro de ayuda
Encuentra recursos de soporte para todas tus necesidades en un solo lugar.