¿Cómo podemos ayudarle hoy?

What value is expected when measuring capacitance of individual capacitors in a Powerlogic PFC capacitor bank?

Issue:

It may not be clear what value is to be expected when measuring capacitance for capacitors in a Powerlogic PFC capacitor bank.

Product Line:

Powerlogic PFC capacitors

Resolution

There will be a uF rating on the label of the capacitor. The L-L measurement taken should be 1.5X the value printed on the capacitor label. The photo below shows a typical label and where this value can be found.

Individual Capacitor label example

Example: BLRCH292A350B57, the capacitance per phase for this capacitor is 93.8uF.  93.8 X 1.5 =140.7uF

You would need to measure line to line (A to B, B to C, and C to A) on the capacitor and the values should be around 140uF -/+5% for each measurement.

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies