¿Cómo podemos ayudarle hoy?

Why do my string displays show squares when the string is coming from my PLC?

Issue:

Why do my string displays show squares when the string is coming from my PLC?

Product Line:

Vijeo Designer, HMIs

Environment:

Vijeo Designer

Resolution:

Why do my string displays show squares when the string is coming from my PLC?

squares showing

Please click into your IO Manager Driver node and check what the "String Encoding" is set as:

IO manager

The default is ASCII and it should be set to ASCII for strings

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric España

Explorar más

Explorar más

¿Necesitas ayuda?

Selector de productos

Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.

Pedir presupuesto

Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.

¿Dónde comprar?

Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.

Centro de ayuda

Encuentra recursos de soporte para todas tus necesidades en un solo lugar.