¿Cómo podemos ayudarle hoy?

Machine Expert V2.3/2.5 - Password Expiration: Default Setting and Configuration

Issue / Symptoms:

Communications using login/password no longer works.

For example, HMI may be disconnected from the machine.

Same for OPC UA, FTP, Web Visu, Web Server connections.

When connecting from Machine Expert, a popup window is displayed saying that the PLC password has expired and requiring setting a new password.

This issue is due to the Password Expiration setting that was introduced in Machine Expert V2.3 and V2.5.

There is no way to determine the default expiration period when the setting remains unchanged from its default value.

Product lines:

M241, M251 and M262 controllers programmed with Machine Expert V2.3 or V2.5.

Resolution:

To confirm the default value for the Password Expiration Timeout Days that is configured in a specific Machine Expert controller, it is required to connect to the specific controller for which this value has not been changed.

For the M241, M251 and M262 controllers, the default value is 365 days. It is possible to change it from 0 to 1000 days.

There are different possibilities to prevent the expiry of the password from accessing the controller:

  • From Machine Expert
  • Via FTP connection
  • By using an SD card

See attached documents.

Note:

In case the password is already expired, only a connection from Machine Expert allows renewing it.

Nevertheless, a solution by using the Clone feature via SD card can be also used but an additional PLC and Machine Expert are required.

See attached procedure.

Schneider Electric España

Documentos adjuntos
Disabling Password Expiration via FTP connection.pdf [81.74 KB]
Disabling Password Expiration from Machine Expert.pdf [127.31 KB]
Disabling Password Expiration using an SD card.pdf [99.79 KB]
How to use the Clone feature to restore a PLC with expired password and disable the expiration password setting.pdf [258.15 KB]
Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Condiciones generales de contratación
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies
  • Centro de Preferencias