Rack PDU 2G, Metered by Outlet with Switching, ZeroU, 20A/208V, 16A/230V, (21) C13 & (3) C19

AP8659

1-Year Secure Network Management Card subscription included
Ideal for Colocation, large data centers or distributed IT sites
Plan capacity and balance loads with +/- 3% metering accuracy (amps, volts, kW, kWh)
Real-time remote monitoring of connected load through EcoStruxure IT and other platforms
Environmental Data
Total lifecycle Carbon footprint
537
Use Better
Packaging made with recycled cardboard
information_stroke
Recycled cardboard content is minimum 70% (50% in US). Some orders may include non-recycled cardboard until stock runs out.
Yes
Energy Efficiency Optimized
information_stroke
The energy efficiency of this Product is at least 10% better than market average or product previous generation.
Energy efficient product
Use Again
Recyclability potential, in %
information_stroke
The calculation of the recyclability potential relies on the scenario "France - parts are shredded" of TR62635 considering all parts in the product and materials recyclability. We recognized that this may not always allow comparison with other competitor offers on the market and are waiting for a common standard to be published end of 2026.
60
Take-back
information_stroke
Whether the product has been included in a global take-back program. Some products are eligible in some geographies, please verify if it's available in your country.
No
+ Lifecycle Services
1 Year Warranty Extension for (1) Accessory (Renewal or High Volume)

WEXWAR1Y-AC-03

Specifications
arrow2_down
Overview
PresentationAPC Metered by Outlet with Switching Rack Power Distribution Units (PDUs) enable advanced, user-customizable power control and individual outlet power metering. Remote outlet level controls allow power on/off functionality for power recycling to reboot locked-up equipment and to avoid unauthorized use of individual outlets. Power sequencing delays allow users to define the order in which to power up or down attached equipment. Avoid circuit overload during power recovery and extend uptime of critical equipment by prioritizing the load shedding. Current metering provides real-time remote monitoring of connected loads. Switched Rack PDUs include real power monitoring, a temperature/humidity sensor port, and locking IEC receptacles. User-defined alarms warn of potential circuit overloads before critical IT failures occur. Users can access, configure, and control Switched rack PDUs through secure Web, SNMP, or Telnet Interfaces and is complimented by APC Centralized Management platforms using InfraStruxure Central, Capacity Manager and Change Manager.
Lead timeUsually in Stock
Main
ColourBlack
Product or component typePDU
PDU typeSwitched metered outlet
Provided equipmentCAN port terminator
Installation guide
Rack mounting brackets
Safety guide
Serial configuration cable
Complementary
Input Voltage200 V
208 V
230 V
Height1829 mm
Width56 mm
Output Voltage100 V
200 V
208 V
230 V
Depth51 mm
Net weight6.09 kg
Mounting locationSide
Mounting preferenceNo preference
Input Plug TypeIEC 60320 C20
Mounting modeRack-mounted
Rack units0U
Mounting positionVertical
[In] rated current16 A
Permissible voltage100…240 V
Input current limits20 A
Load capacity3300 VA
Network frequency50/60 Hz
Outlet type and quantity21 IEC 60320 C13
3 IEC 60320 C19
Environment
Product certificationsPSE
UL listed
VCCI class A
VDE
StandardsEN 55022 class A
EN 55024
EN 61000-3-2
EN 61000-3-3
FCC part 15 class A
ICES-003
Ambient air temperature for operation-5…60 °C
Relative humidity5…95 %
Operating altitude0...10000 ft
Ambient air temperature for storage-25…65 °C
Storage Relative Humidity5…95 %
Storage altitude0…15240 m
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height203.8 cm
Package 1 Width16.2 cm
Package 1 Length11.7 cm
Package 1 Weight8.342 kg
Contractual warranty
Warranty2 years repair or replace
arrow2_down
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental footprint
Use Better
Materials and Substances
Energy efficiency
Use Again
Repack and remanufacture
Documents
arrow2_down
Software and Firmware
arrow2_down

Need more information? Check our technical FAQs!

Easily find answers to the most frequently asked questions.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Need help? Start here
  • Where to buy
  • Careers
  • Company Profile
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Data Privacy
  • Cookies Policy
  • Terms of use
  • Change your cookie settings