Circuit breaker ComPacT NSX160N, 50kA at 415VAC, MicroLogic 2.2 trip unit 160A, 3 poles 3d

C16N32D160

Poles description:

[In] rated current:

Breaking capacity:

Trip unit name:

Environmental Data
Total lifecycle Carbon footprint
167
Use Better
Packaging made with recycled cardboard
information_stroke
Recycled cardboard content is minimum 70% (50% in US). Some orders may include non-recycled cardboard until stock runs out.
Yes
Use Again
Recyclability potential, in %
information_stroke
The calculation of the recyclability potential relies on the scenario "France - parts are shredded" of TR62635 considering all parts in the product and materials recyclability. We recognized that this may not always allow comparison with other competitor offers on the market and are waiting for a common standard to be published end of 2026.
54
Take-back
information_stroke
Whether the product has been included in a global take-back program. Some products are eligible in some geographies, please verify if it's available in your country.
No
Description
arrow2_down
This ComPacT NSX160N is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 50KA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.2 trip unit, with 160A rating. MicroLogic 2.2 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX160N is part of Schneider Electric EcoStruxure Power architecture.
Specifications
arrow2_down
Main
RangeComPacT
Product nameComPacT NSX
Device short nameNSX160N
Product or component typeCircuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current160 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1
50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1
10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity codeN 50 kA 415 V AC
Trip unit nameMicroLogic 2.2
Trip unit technologyElectronic
Trip unit protection functionsLSoI
Control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability40000 cycles
Electrical durability40000 cycles at 440 V In/2
20000 cycles at 440 V In
15000 cycles at 690 V In/2
7500 cycles at 690 V In
Power dissipation per pole9.2 W
Mounting supportBackplate
Mounting positionHorizontal and vertical
Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
Trip unit rating160 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range63...160 A
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range400 s at 1.5 x Ir
16 s at 6 x Ir
11 s at 7.2 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range2400 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
Net weight2.2 kg
Environment
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating
2000 m...5000 m with derating
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height14.000 cm
Package 1 Width11.000 cm
Package 1 Length19.200 cm
Package 1 Weight1.873 kg
Unit Type of Package 2S03
Number of Units in Package 27
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight13.493 kg
arrow2_down
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental footprint
Use Better
Materials and Substances
Use Longer
Lifetime extension
Use Again
Repack and remanufacture
Documents
arrow2_down
Software and Firmware
arrow2_down
arrow2_down

Need more information? Check our technical FAQs!

Easily find answers to the most frequently asked questions.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Contact Support
  • Find our Offices
  • Need help? Start here
  • Where to buy
  • Careers
  • Company Profile
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Data Privacy
  • Cookies Policy
  • Terms of use
  • Change your cookie settings