LR9F7375
Discontinued on:31 Dec 2023
Recommended replacement(s)
Environmental Data
Total lifecycle Carbon footprint
355
Use Better
Packaging made with recycled cardboard
No
Use Again
Take-back
No
TeSys LR9F electronic overload relay, thermal setting range 200-330A, class 10, for protection of motors 132-160kW@400V. to be mounted directly below a TeSys F 3-pole contactor LC1 F225, F265, F330, F400, F500, use of a support mounting plate LA7F902 is mandatory (to be ordered separately). Motor protection includes thermal overload of 1-phase and 3-phase motors, phase failure, phase unbalance, prolonged starting times, stalled rotor conditions. On the front of the relay, it provides a thermal adjustement dial, buttons for test, stop & reset, a trip indicator, trip auxiliary contacts 1NO+1NC. Multi standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).
Range | TeSys |
---|---|
Product name | TeSys LRF |
Device short name | LR9F |
Product or component type | Electronic thermal overload relay |
Relay application | Motor protection |
Product compatibility | LC1F225...LC1F500 |
Network type | AC |
Thermal overload class | Class 10 conforming to IEC 60947-4 |
Thermal protection adjustment range | 200…330 A |
Network frequency | 50/60 Hz |
---|---|
Mounting support | Direct on contactor Plate |
Tripping threshold | 1.12 +/- 0.06 In tripping conforming to IEC 60947-4-1 |
Surge withstand | 4 kV conforming to IEC 61000-4-5 |
Contacts type and composition | 1 NO + 1 NC |
[Ith] conventional free air thermal current | 5 A for control circuit |
[Ue] rated operational voltage | 1000 V AC 50/60 Hz for power circuit conforming to VDE 0110 group C |
[Ui] rated insulation voltage | Power circuit: 1000 V AC conforming to IEC 60947-4 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-1 |
Phase failure sensitivity | Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1 |
Reset | Manual reset on front relay |
Control type | Dial white full-load current adjustment Test button red Push-button red reset Push-button stop |
Local signalling | Trip indicator |
Temperature compensation | -20…70 °C |
Current consumption | <= 5 mA no-load |
switching capacity for alarm | 0...150 mA |
Maximum voltage drop | <2.5 V closed state |
Connections - terminals | Control circuit: screw clamp terminals 1 cable 0.75…2.5 mm² - cable stiffness: flexible - with cable end Control circuit: screw clamp terminals 1 cable 0.75…2.5 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 cable 0.75…4 mm² - cable stiffness: flexible - without cable end Control circuit: screw clamp terminals 2 cable 1…1.5 mm² - cable stiffness: flexible - with cable end Control circuit: screw clamp terminals 2 cable 1…2.5 mm² - cable stiffness: flexible - without cable end Control circuit: screw clamp terminals 2 cable 1 mm² - cable stiffness: solid Power circuit: lugs-ring terminals M10 |
Tightening torque | Control circuit: 1.2 N.m on screw clamp terminals Power circuit: 35 N.m on screw clamp terminals |
Height | 136.8 mm |
Width | 150 mm |
Depth | 127.6 mm |
Net weight | 2.32 kg |
Standards | VDE 0660 IEC 60947-4-1 EN 60947-4-1 IEC 60255-17 IEC 60255-8 |
---|---|
Product certifications | UL CSA UKCA |
Protective treatment | TH |
IP degree of protection | IP20 conforming to IEC 60529 IP20 conforming to VDE 0106 |
Ambient air temperature for operation | -20…55 °C conforming to IEC 60255-8 |
Ambient air temperature for storage | -40…85 °C |
Operating altitude | <= 2000 m without derating |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Mechanical robustness | Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7 Vibrations 5...300 Hz: 2 GN conforming to IEC 60068-2-6 |
Dielectric strength | 6 kV 50 Hz conforming to IEC 255-5 |
Electromagnetic compatibility | Resistance to electrostatic discharge: 6 kV in indirect mode conforming to IEC 61000-4-2 Resistance to electrostatic discharge: 8 kV in air conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test: 10 V/m conforming to IEC 61000-4-3 Fast transients immunity test: 2 kV conforming to IEC 61000-4-4 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 18.000 cm |
Package 1 Width | 20.000 cm |
Package 1 Length | 19.500 cm |
Package 1 Weight | 1.882 kg |
Unit Type of Package 2 | P06 |
Number of Units in Package 2 | 36 |
Package 2 Height | 75.000 cm |
Package 2 Width | 60.000 cm |
Package 2 Length | 80.000 cm |
Package 2 Weight | 79.896 kg |
Warranty | 12 months |
---|
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Total lifecycle Carbon footprint
355
Environmental Disclosure
Use Better
Packaging made with recycled cardboard
No
Packaging without single use plastic
No
Compliant with Exemptions
SCIP Number
D5a17874-1166-4927-b008-33d15e304a41
REACh Regulation
PVC free
Yes
Use Again
End of life manual availability
Take-back
No
WEEE Label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.
LR9F7375 is replaced by: