Issue:
Can I program drive to switch between different set points on PID controller for the ATV630 drive?
Product Line:
ATV630
Environment:
All models, all serial numbers
Cause:
Customer wanted to easily switch between three set points, 40, 60 and 80 PSI.
Resolution:
Under the main menu, enter complete setting -> Pump Functions -> PID Controller -> PID Reference -> PID preset references:
Assign a digital input (DI5) for 2 PID Preset Assign
Enter 40PSI for RefPID Preset 2
Assign a digital input (DI6) for 4 PID Preset Assign
Enter 60PSI for RefPID Preset 3
Enter 80PSI for RefPID Preset 4
Note: This function can be accessed if [PID feedback ass.] PIF is assigned.
Can I program drive to switch between different set points on PID controller for the ATV630 drive?
Product Line:
ATV630
Environment:
All models, all serial numbers
Cause:
Customer wanted to easily switch between three set points, 40, 60 and 80 PSI.
Resolution:
Under the main menu, enter complete setting -> Pump Functions -> PID Controller -> PID Reference -> PID preset references:
Assign a digital input (DI5) for 2 PID Preset Assign
Enter 40PSI for RefPID Preset 2
Assign a digital input (DI6) for 4 PID Preset Assign
Enter 60PSI for RefPID Preset 3
Enter 80PSI for RefPID Preset 4
Note: This function can be accessed if [PID feedback ass.] PIF is assigned.
Gepubliceerd voor: Schneider Electric Netherlands


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.