Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
If the lugs on a breaker are 90 degree C rated, can I use 90 degree C wire at its rated ampacity?
Issue:​
90 degree C wire at it's rated ampacity for 90 degree C rated breaker.

Product Line:
Circuit Breakers

Resolution:
No. The 2011 NEC defines the temperature rating for circuit breakers as follows:
Per NEC 110.14 (C)(1)(b), the termination temperature rating for breakers rated above 100 A or marked for conductors larger than #1 AWG is 75 deg. C. Note that higher temperature rated insulation (such as 90 deg. C) is permissible, but the wire must be sized per the 75 deg. C column of Table 310.15(B)(2)(b) in the 2011 NEC.

Per NEC 110.14 (C)(1)(a) the temperature rating for breakers rated 100 A or less is 60 deg. C unless otherwise marked.

Schneider Electric New Zealand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings