Can the ATV312 Drive Be Configured with a 3-Contactor Bypass System?

Resolution:

Yes. Although the ATV312 is not available as an enclosed product with a built-in bypass option, it can be integrated into a 3-contactor bypass configuration.

In this setup:

  • The Isolation Contactor (IC) and Bypass Contactor (BC) are controlled by an external control circuit.
  • The Drive Output Contactor (DOC) is controlled by the ATV312 using an output relay assigned to the Run Status function.
  • A DOC auxiliary contact should be wired as a run-permissive input to the drive to ensure proper operation.

Refer to the attached wiring diagram for an example of a typical 3-contactor bypass configuration.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric New Zealand

Attachment(s)
VFD eg 3 contactor bypass.pdf [164.8 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings