Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How does the SGR Sensor, MDGF module work with Micrologic X?

For the below systems as described in the MDGF instruction sheet
SGR Sensor
Please find below how the current sensor, MDGF works with Micrologic :

If a primary current of 100A passes through the SGR current sensors, then a secondary current of 0.1A will be received by the MDGF summing module via terminals 1(J1-1) and 3(J1-3).

The MDGF summing module internally does the following calculation :

100A(rms)*0.00173 = 0.173V(rms) : this voltage can be measured on the terminal 5(J2-2) and 7(J3-1) of the MDGF summing module and it is transmitted to the terminals M2 and M3 of the micrologic Trip Unit.

The Micrologic does the following calculation : 0.173V(rms)/0.00173(rms) = 100A

The Micrologic will report the Ig trip if the current from the current sensor and MDGF exceeds the Ig threshold and the tg time delay expires

Information on wiring and installation can be found in the instruction sheet - https://download.schneider-electric.com/files?p_enDocType=Instruction+sheet&p_File_Name=NHA92405-02.pdf&p_Doc_Ref=NHA92405

For the MTZ spare part list refer to the latest spare part catalogue - https://download.schneider-electric.com/files?p_Doc_Ref=COM-POWER-LVMKT215EN

Schneider Electric New Zealand

Explore more
Explore more
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.