Is it possible replace a PRM without Control Expert?

Yes, it is possible.

In theControl Expert application, under PRM general settings, ensure the following options are checked and properly configured:

  • Create an entry for this device name in the DHCP server
  • Backup the PRM configuration in the FDR server on download

Once these settings are confirmed, follow these steps to correctly replace the PRM:

  1. Remove the PRM module to be replaced.
  2. Prepare the new PRM module:
    • Set its lower rotary switch to ‘E’ (Configuration file deletion) to clear any existing configuration.
    • Power up the new PRM and wait for the boot process to complete, then power it off.
  3. Match the rotary switch positions:
    • Check the rotary switch positions on the old PRM and set the new PRM identically.
  4. Install the new PRM:
    • Power up the new PRM in the same location as the old one.

The new PRM will boot and automatically retrieve its configuration file from the FDR server.

Schneider Electric New Zealand

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings