Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
M580 CPU DTM Configuration Validation Failed

Issue:

When trying to add a new Rack in Control Expert , the following message DTM message BMEP58_ECPU_EXT:

Configuration validation failed ! Details :

Control Expert DTM message

Product Range:

M580 CPU.

Resoultion:

Please go to the Corresponding Modbus Device in Device List then double click the Device and go to Request Setting

and see whether the Health Time Out (ms) is greater than Repetitive Rate

Schneider Electric New Zealand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings