ION Setpoint module- How will the module behave if both the high and low limit are set to the same value for either greater than or less than comparison? Will this cause any issues?

Resolution:

When you set both the high and low limits to the same value, the meter effectively has zero deadband. This can lead to constant triggering and rapid toggling of the setpoint outputs, depending on how the measured value hangs around that threshold.

  1. The Pickup and Dropout settings define triggers based on threshold crossings (Over and under conditions).
  2. I would suggest always adding a small buffer between the high and low limits (e.g., High = 20, Low = 15).

While setting both limits to the same threshold is technically allowed, it is generally poor design/configuration and this removes essential deadband, which can compromise the accuracy of your outputs.

Schneider Electric New Zealand

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings