During PAS600 commissioning with a PM5100, a Network Configuration Error occurred during data publication despite working data sampling and a 4G/5G modem connection.

Issue

During PAS600 commissioning with a PM5100, a Network Configuration Error occurred during data publication despite working data sampling and a 4G/5G modem connection.

Product Line

Panel Server (PAS600) (PAS800)

Environment

- PAS600 Panel Server

- PM5100 Power Meter

- Teltonika RUT241 4G/5G Modem

- Cloud publication using default PAS network settings (DHCP)

Resolution

Here the issue is not with the PAS600 Panel Server. The root cause was the 4G modem configuration. If customer is using a Teltonika RUT241, which is normally plug-and-play when both PAS and modem remain at default network settings. However, depending on the SIM provider or device pre-configuration, additional changes may be required in the modem settings to allow for cloud publication.

For fully plug-and-play operation, use a modem procured via Madison Technologies with a Telstra IoT SIM.

Required Modem Settings

1. PDP Type: Set to IPv4

2. Ensure required ports (as shown in screenshots) are enabled.

3. PAS600 must remain at default DHCP settings.

4. Power cycle the PAS600 after any modem configuration changes, ensuring only the modem is connected via Ethernet during startup.

5. Best practice: Connect the PAS600 and modem directly via Ethernet on first startup before connecting a laptop.

The settings that need to be changed are in the screenshots below:

Image-1

Image-2

Image-3

Schneider Electric New Zealand

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings