In PM5320 is it possible to change the Modbus ID from 255 when connecting via ethernet so that it can be integrated to SCADA
Product Line:
METSEPM5320
Resolution:
PM5320 have ethernet with Modbus TCP/IP. 255(0xFF in Hex) is not the device address. It's the unit identifier.
As per Modbus TCP/IP standards, unit id for standalone meter should be 255. The unit id of PM5320 and PM5340 meter is 255 and it cannot be changed.
You can see the excerpt below taken from Modbus standard