How to troubleshoot if a Zelio Relay has a flashing/flickering screen.
Issue:
A Zelio Relay has a screen that is flashing/flickering.
Troubleshooting Steps:
1. 24V power supply:
- Measure the voltage directly at the Zelio terminals with the loads activated. (No temporary drop < 22V and no overvoltage > 28V).
- Check the 24V wiring (length, cross-section, tightness).
2. EMC interference from the environment, Eg: VSDs, Pumps, Generators, Motors etc:
- Move contactors, relays, solenoid valves, etc., away from the Zelio.
- Verify that no high-power motor cables run alongside the Zelio cables and check that the control box is properly grounded.
3. Zelio inputs:
- Test operation with intermediate relays (galvanic isolation).
4. Temperature:
- Measure the temperature inside the control box, near the Zelio. Verify that the temperature remains below 40°C during continuous operation.
5. Load tests, if there are multiple controlled units/equipments connecting to Zelio Relay:
- Run all controlled equipments simultaneously while monitoring the supply voltage.
- Test by powering those controlled equipments one at a time to identify the issued equipment.
- Perform a test with relays or optocouplers on all 3 inputs.