Issue:
ATV630 ramp switching set up.
Product Line:
Altivar 630
Environment:
All
Cause:
Dual ramp speeds up to full speed
Resolution:
Under drive menu go into Complete settings menu.
Go into the Generic functions Menu and select Ramp switching
There are 2 ways of doing ramp switching:
The first ramp is followed by acceleration and deceleration parameters.
The second ramp is followed by acceleration 2 and deceleration 2 located under Ramp switching submenu.
ATV630 ramp switching set up.
Product Line:
Altivar 630
Environment:
All
Cause:
Dual ramp speeds up to full speed
Resolution:
Under drive menu go into Complete settings menu.
Go into the Generic functions Menu and select Ramp switching
There are 2 ways of doing ramp switching:
Using frequency threshold
Ramp 2 thd (FRT) is where you would assign a frequency for second ramp to take over.
Using a logic input to switch ramp
Ramp Switch Assign (RPS) is used if a logic input is preferred to be toggled for the second ramp to take over.
Ramp 2 thd (FRT) is where you would assign a frequency for second ramp to take over.
Using a logic input to switch ramp
Ramp Switch Assign (RPS) is used if a logic input is preferred to be toggled for the second ramp to take over.
The first ramp is followed by acceleration and deceleration parameters.
The second ramp is followed by acceleration 2 and deceleration 2 located under Ramp switching submenu.
Publicado para: Schneider Electric Portugal




Precisa de ajuda?
Ferramenta de seleção de produtos
Encontre rápida e facilmente os produtos e acessórios certos para as suas aplicações.
Obter um Orçamento
Inicie o seu pedido de contacto online e um especialista irá contactá-lo.
Onde adquirir?
Encontre facilmente o distribuidor mais próximo da Schneider Electric perto de si.
Centro de ajuda
Encontre recursos de apoio para todas as suas necessidades, num único local.