Why float type tags are not read correctly in EcoStruxure Machine SCADA Expert through OPCUA?
The article is applicable for EcoStruxure Machine SCADA Expert 2020 minimum
The behaviour is visible only in computer in european environment. The comma is not reconized correctly.
To fix the issue, download and follow the step:
File: https://schneiderelectric.sharepoint.com/:u:/s/BoxSupportL3Group/EQDJl9WHNwNBqAbS_vY_bikBCWpnFptgtu_a8i07q1qpwA?e=QUBY1u
- Close and Stop any instance of EMSE.
- Unzip the folder.
- Rename the current file < OPCUAClient.dll > to < OPCUAClient_old.dll > into the folder: < C:\Program Files (x86)\........... >
- Copy/Paste the unzipped file (OPCUAClient.dll) on < Bin > folder
Publicado para: Schneider Electric Portugal










Precisa de ajuda?
Ferramenta de seleção de produtos
Encontre rápida e facilmente os produtos e acessórios certos para as suas aplicações.
Obter um Orçamento
Inicie o seu pedido de contacto online e um especialista irá contactá-lo.
Onde adquirir?
Encontre facilmente o distribuidor mais próximo da Schneider Electric perto de si.
Centro de ajuda
Encontre recursos de apoio para todas as suas necessidades, num único local.