{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.
Hur kan vi hjälpa dig idag?
What is the difference between ModSoft PID function and Concept PID function.

The difference between ModSoft PID and Concept PID loops are as follows:

PID (ModSoft):
PB - Gain = 100 / PB
I - Integral Coefficient Expressed as Repeats/Minute. The higher the value, the greater the integral contribution
D – Derivative Coefficient. Expressed in Minutes. The higher the value, the greater the derivative contribution
PID (Concept):
GAIN - Enter GAIN value as a REAL. Can be Positive or Negative. Positive Gain = Direct acting loop. Negative Gain = Reverse acting loop
TI - Integral Time. Expressed as TIME. The smaller the unit of time, the more significant the integration
TD - Derivative Time. Expressed as TIME. The greater the unit of time, the greater the derivative contribution.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Artiklar som kan vara till nytta
Utforska mer
Produktfamilj