Hur kan vi hjälpa dig idag?
On the ATV212 drive, what causes the drive to display nSt?
Issue:
Getting a nSt fault on a ATV212 drive..
Product Line:
ATV212
S-Flex
Environment:
nst
Cause:
n/a
Resolution:
nSt is NOT a fault.
It is a status indicating the drive is not able to run, normally caused by modifying the programming of the drive while the drive is running.
Most parameters cannot be changed while the motor is running.
If such a parameter is changed when the motor is running, the drive will freewheel stop and the display will flash nSt.
Cycle power to reset the status.
Getting a nSt fault on a ATV212 drive..
Product Line:
ATV212
S-Flex
Environment:
nst
Cause:
n/a
Resolution:
nSt is NOT a fault.
It is a status indicating the drive is not able to run, normally caused by modifying the programming of the drive while the drive is running.
Most parameters cannot be changed while the motor is running.
If such a parameter is changed when the motor is running, the drive will freewheel stop and the display will flash nSt.
Cycle power to reset the status.
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.