Video: How is standard basic programming performed on an ATS48?
Issue:
How is an ATS48 set up for basic programming?
Product line:
Altistart 48
Environment:
All models, all serial numbers
Cause:
Basic programming set up for the ATS48 soft starters.
Resolution:
SET menu:
IN= FLA motor amps
ACC= acceleration
STY= type of stop (f=freewheel, d=ramp stop, b=intel braking)
DEC= deceleration [only appears if Sty= d (ramp stop)]
ILT=current limit 400% or 4X your motor current is default value.
DRC menu:
CLP= Off (Torque Control). This is important if the ACC/DEC times have to be followed exactly.
Refer to the ATS48 User Manual for any further details.
The following video demonstrates this initial setup procedure:
How is an ATS48 set up for basic programming?
Product line:
Altistart 48
Environment:
All models, all serial numbers
Cause:
Basic programming set up for the ATS48 soft starters.
Resolution:
SET menu:
IN= FLA motor amps
ACC= acceleration
STY= type of stop (f=freewheel, d=ramp stop, b=intel braking)
DEC= deceleration [only appears if Sty= d (ramp stop)]
ILT=current limit 400% or 4X your motor current is default value.
DRC menu:
CLP= Off (Torque Control). This is important if the ACC/DEC times have to be followed exactly.
Refer to the ATS48 User Manual for any further details.
The following video demonstrates this initial setup procedure:
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.