What is the CFF fault on the ATS48 soft starter and what causes it?

Issue:
What is the cause of the CFF fault on the ATS48 soft starter?

Product Line:
Altistart 48, ATS48

Environment:
All models, all serial numbers.

Cause:
Invalid configuration on power up.  This could be due to a replaced control board or electrical interference that prevents the control board from reading the configuration.

Resolution:
This fault is due to an Internal configuration error.
Complete a Factory Reset by going to drC menu > FCS parameter> change to YES.  Hold Enter button for 2s to complete this reset.  Reprogram the softstart.
Cycle power to the softstart.  Then provide a new run command.
If the fault persists after these steps, replace the control board or Softstart as applicable.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

  • Produktväljare

    Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

  • Begär en offert

    Ställ din fråga online så kontaktar vi dig.

  • Här köper du

    Hitta enkelt närmaste Schneider Electric-distributör på din ort.

  • Hjälpcenter

    Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings