Hur kan vi hjälpa dig idag?

MV-90: Meter Events

Issue:

How to retrieve meter events in MV‑90 and decode the events that MV‑90 reports.

Product Line:

MV‑90

Environment:

Meter Events

TIM: Translation/Interface Module

Cause:

Event codes/Descriptions can differ between what the meter records and what MV‑90 shows, and not all events may be retrieved directly. Conversion/mapping depends on the TIM.

Resolution:

About event retrieval

  • The TIM automatically reads the meter Event Log for the same time period as an All/Partial Read.

To retrieve events:

  1. Perform an All/Partial Read.
  2. Go to Meter Events → Event Maintenance → choose the RecorderID.
  3. Change the Start Date to an earlier date → Go.

About decoding MV‑90 event codes:

  • Refer to the latest TIM_Appnote in:
    C:\MV90xi\TIMs (contains conversion of ION events to MV‑90 events).

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings