ION Enterprise web based report prompts to enter a user name and password to access the data source.

Issue
When attempting to generate a web based report there is a prompt for entering a user name and password to access the data source:

Web Reporter User Name and Password Prompt

Product Line
ION Enterprise 6.x

Environment
Reporting

Cause
Login credentials are changed or may not be specified so that WebReporter (Reporting Services) can access the IONReportDataSource.

Resolution
Follow the procedure below to set the correct login credentials.
1.Open the web browser and open the http://<server name>/Reports or http://<server name>/Reports$ION virtual root.
2. Open the IONReportDataSource.
3. Under the Connect Using, select the radio button "Credentials stored securely in the report server".
4. Enter the following user information:
User Name: IONUser
​Password: IONisgreat!
5. Click on Apply to apply the changes.

User Name and Password Steps

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings