Hur kan vi hjälpa dig idag?

How to connect Unity Pro to a Modbus PLC through a TSXETG100 Ethernet gateway

Issue

How can Unity Pro connect to a Modbus PLC through a TSXETG100 Ethernet gateway?

Product Line

  • TSXETG100
  • Unity Pro

Environment

The TSXETG100 is used as the communication gateway between Unity Pro and the PLC.

Resolution

  1. Configure the PLC Modbus address in the TSXETG100

    • Open the TSXETG100 web interface by entering its IP address in a web browser.

ETG0100, connection

      • Log in to the TSXETG100.
      • Select Setup > Device List.

web page, ETG,

      • Add the Modbus address of the PLC to the device list.
      • Select Apply to save the configuration.
  1. Configure the PLC address in Unity Pro

    • Open the Unity Pro project.
    • Select PLC > Set Address.
    • unity Pro, Set address
    • In Media, select TCPIP.
    • In the Address field, enter the TSXETG100 IP address followed by a semicolon (;) and the PLC Modbus address.
    • connection configuration

    In this example:

    • 192.168.40.2 is the TSXETG100 IP address.
    • 1 is the Modbus address of the PLC.
  2. Connect to the PLC

    • Confirm the address configuration.
    • Select PLC > Connect.


Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Allmänna affärsvillkor
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings
  • Inställningscenter