Hur kan vi hjälpa dig idag?

How do I reset a TCSESM ConneXium Ethernet Managed Switch to factory default settings using Hyper Terminal?

Issue

How can a TCSESM ConneXium Ethernet Managed Switch be reset to its factory default configuration using a serial connection?

Important: Resetting the switch to factory defaults erases the existing configuration.

Product Line

  • TCSESM ConneXium Ethernet Managed Switch

Environment

The procedure described here uses:

  • 490NTRJ11 serial external management cable
  • PC with a serial COM port
  • HyperTerminal
  • Serial communication settings:
    • Baud rate: 9600
    • Data bits: 8
    • Parity: None
    • Stop bits: 1
    • Flow control: None

Resolution

  1. Connect the PC to the TCSESM switch using the 490NTRJ11 serial external management cable.

  2. Start HyperTerminal.

windows hyper terminal

  1. Create a new connection and select the COM port connected to the switch.

new connectionCOM selection

  1. Configure the COM port as follows:

    • 9600 baud
    • 8 data bits
    • No parity
    • 1 stop bit
    • No flow control
    COM properties
  2. Power-cycle the TCSESM switch.
  3. During startup, wait for the following message:

    "Press <1> to enter System Monitor 1..."

reboot TCSESM hyperterminal

  1. Press 1 within approximately 2 seconds.

    If the System Monitor is not entered, power-cycle the switch and repeat the procedure.

  2. From the System Monitor menu, press 5 to select:

    Erase main configuration file

  3. When prompted to press RETURN to delete the configuration or ESC to cancel, press RETURN.

SysMon Hyperterminal

  1. Wait for confirmation that the main configuration file has been deleted, then press any key to continue.

Reset configuration, TCSESM

  1. From the System Monitor menu, press 4 to select:

    End (reset and reboot)

reboot , TCSESM

  1. During the subsequent restart, do not press 1 when the following message appears:

    "Press <1> to enter System Monitor 1..."

back to factory, TCSESM

  1. Allow the switch to complete its normal startup.
The switch should then start with its factory default configuration.

TCSESM with default configuration

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Allmänna affärsvillkor
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings
  • Inställningscenter