Why can't I connect to Zelio SR2/SR3 device using a bluetooth interface SR2BTC01? I’m getting error popup window DC46_10
Issue:
What are the components of VBD1?
Product Line:
Operating Mechanism and Disconnect Switches
Cause:
SR3B261FU connection issues Error code DC46_10
Within the year 2014 a new hardware design has been made for the SR2BTC01 interface.
Resolution:
To identify if your device is a new one or old design -- there is no version indication -- a DOM ( manufacturing date ) within the year 2014 or later indicates the new design.
In order to be able to have the ZelioSoft v4.5 version running correctly with this hardware level, we need to install a new version of the M2Dc47_Comm.dll file ( dated April 2014, attached into this FAQ)
This standard M2Dc47_Comm.dll file to be replaced is located in the ZelioSoft2 V.4.5 directory (by default 'C:\Program Files\Schneider Electric\Zelio Soft 2)
What are the components of VBD1?
Product Line:
Operating Mechanism and Disconnect Switches
Cause:
SR3B261FU connection issues Error code DC46_10
Within the year 2014 a new hardware design has been made for the SR2BTC01 interface.
Resolution:
To identify if your device is a new one or old design -- there is no version indication -- a DOM ( manufacturing date ) within the year 2014 or later indicates the new design.
In order to be able to have the ZelioSoft v4.5 version running correctly with this hardware level, we need to install a new version of the M2Dc47_Comm.dll file ( dated April 2014, attached into this FAQ)
This standard M2Dc47_Comm.dll file to be replaced is located in the ZelioSoft2 V.4.5 directory (by default 'C:\Program Files\Schneider Electric\Zelio Soft 2)
Publicerad för: Schneider Electric Sverige


Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.