what are the OIDs for reading the port link status from Connexium Ethernet Switch TCSESM083F23F1 using SNMP Protocol in a MIB browser.
Issue:
Customer wants to use SNMP protocol to read port status of the ethernet switch
Product Line
Connexium Ethernet Switch TCSESM083F23F1
Environment:
Windows 7 Pro
Resolution:
The very first step is to install the correct MIB file in the MIB Browser.
We need to install the two files in the MIB Browser.
1.SchneiderTFE-V03-00.mib
2.SchneiderElectricSwitches_V02_00.mib.
Contact your local country Schneider Electric Customer Care Center to get this files.
The port status can be up(1), down (2).
The OID for reading the port status is read as below.
Port x >> oid=".1.3.6.1.2.1.2.2.1.8.x"
Where "x" denotes the number of port in the switch.
Customer wants to use SNMP protocol to read port status of the ethernet switch
Product Line
Connexium Ethernet Switch TCSESM083F23F1
Environment:
Windows 7 Pro
Resolution:
The very first step is to install the correct MIB file in the MIB Browser.
We need to install the two files in the MIB Browser.
1.SchneiderTFE-V03-00.mib
2.SchneiderElectricSwitches_V02_00.mib.
Contact your local country Schneider Electric Customer Care Center to get this files.
The port status can be up(1), down (2).
The OID for reading the port status is read as below.
Port x >> oid=".1.3.6.1.2.1.2.2.1.8.x"
Where "x" denotes the number of port in the switch.
Publicerad för: Schneider Electric Sverige
Bilagor
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.