Hur kan vi hjälpa dig idag?
Why is ENM8.3 not filtering low priority tags from PME8 system
Issue
Why is ENM8.3 not filtering low priority tags from PME8 system
Product Line
Power Monitoring Expert 8.x
ENM v8.3
Environment
ENM Configuration
Cause
Alarm Configurator in PME is used to build various alarm rules by assigning priorities 100 and higher. ENM configuration of the PME alarms are working as expected; however, meter events from PME with priorities as low as 10 are being sent out to the subscriptions recipients.
Resolution
In ENM Configuration, select Subscriptions Recipients and confirm which Tag Filter is selected. ENM by defaul,t has all low priority and high priority events from PME. If the Tag Filter "All" is selected in the subscription, then all events will be sent out to the subscription's recipients.
For each subscription recipient, build the subscription by using the Add Subscription for each Tag filter in the system, except the tag filter "All"
NOTE: Starting in PME2020, the ENM function has been embedded within the PME web application https://www.se.com/us/en/faqs/FA403988/
Publicerad för: Schneider Electric Sverige
Utforska mer
Produkt:
Utforska mer
Produkt:
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.