PME as an EWS server connected with SoapUI as an client got Error message 401.2

Issue:
When using PME as EWS server and SoapUI as an EWS client,SoapUI got the following error message:

<b> Error message 401.2 .: </b>Unauthorized: Logon failed due to server configuration. &nbsp;Verify that you have permission to view this directory or page based on the credentials you supplied and the authentication methods enabled on the Web server. &nbsp;Contact the Web server's administrator for additional assistance.<br><br>

Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0

Cause:
This behavior is caused by Unauthorized, you have to put in the user name and password which has been authorized.

Resolution:
In SoapUI client, put in the username and password (e.g. username = supervisor; pw = 0​), every time before you use any Method or brose the items:
a

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

  • Produktväljare

    Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

  • Begär en offert

    Ställ din fråga online så kontaktar vi dig.

  • Här köper du

    Hitta enkelt närmaste Schneider Electric-distributör på din ort.

  • Hjälpcenter

    Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings