Hur kan vi hjälpa dig idag?
ENM Monitoring and Diagnostics pages display "[Invalid Date]" for timestamps
Issue
The Event Notification Module (ENM) Monitoring and Diagnostics pages display [Invalid Date] in timestamp columns instead of the actual timestamp.
Product Line
ENM 8.3.x
Environment
PowerSCADA Expert 8.1
Power Monitoring Expert 8.1
Cause
Some Windows locales use special characters for AM/PM notation (e.g., Italian [Switzerland], Chinese [Singapore]). When Windows is configured to use one of these locales, ENM cannot properly format timestamps, resulting in [Invalid Date].
Resolution
Change the Windows locale to one that uses standard AM/PM characters.
Examples:
- Italian (Italy)
- Chinese (China)
Steps:
- Open Control Panel → Region and Language.
- Change the locale to a supported setting.
- Restart ENM services if necessary.
Notes
- This issue applies only to ENM 8.x and PME 8.1.
- Newer versions of PME and ENM have resolved this locale parsing issue.
Recommendation
If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.