Unity Pro, what is occurring on Save/Restore Data containing forced bit?
Saving data containing forced bit by the command «PLC/Save Data From PLC to file» save also the Forced state of these bit .
When these bit will be restored by the command «PLC/Restore Data From to file to PLC»  they will be restored in Forced state.
Nevertheless the list of forced bit will not be restored and in final bit will be forced in the application without knowing easily which ones.
So it is strongly recommended to do not save data with forced bit in the application.

This behavior is always present in Unity Pro V11.1  it is planned to be fixed in a next version.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

  • Produktväljare

    Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

  • Begär en offert

    Ställ din fråga online så kontaktar vi dig.

  • Här köper du

    Hitta enkelt närmaste Schneider Electric-distributör på din ort.

  • Hjälpcenter

    Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings