Magelis boots up slow due to some datalogging files (Dxxxxxx_OLD.dat)
Issue:
Magelis boots up slow due to some datalogging files (Dxxxxxx_OLD.dat)
Product Line:
XBTGC/GK/GT, HMIGTO/GTU/STO/STU, iPC
Resolution:
The data logging system has a mechanism to check the integrity of the data logging files. In the event it detects:
1) Corrupt data
2) Incompatible log formats (ie from an older version)
3) Data that was logged with a date or time in the future (ie, the clock was accidentally moved forward and then backwards)
the file will be renamed DXXXXXX_OLD.dat
The datalogging system will check these 3 conditions each time. Of course on an empty CF/SD card or USB flash drive, these conditions don't exist, so the boot up time is fast. However, if there is lots of data on the card, it will take a long time.
We recommend retrieving the data on the flash drive and format the drive.
Magelis boots up slow due to some datalogging files (Dxxxxxx_OLD.dat)
Product Line:
XBTGC/GK/GT, HMIGTO/GTU/STO/STU, iPC
Resolution:
The data logging system has a mechanism to check the integrity of the data logging files. In the event it detects:
1) Corrupt data
2) Incompatible log formats (ie from an older version)
3) Data that was logged with a date or time in the future (ie, the clock was accidentally moved forward and then backwards)
the file will be renamed DXXXXXX_OLD.dat
The datalogging system will check these 3 conditions each time. Of course on an empty CF/SD card or USB flash drive, these conditions don't exist, so the boot up time is fast. However, if there is lots of data on the card, it will take a long time.
We recommend retrieving the data on the flash drive and format the drive.
Publicerad för: Schneider Electric Sverige
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.