How do I access the embedded web page on an ATV630 drive?

Issue:
Embedded web page in an ATV630

Product Line:
ATV600 process drive including:
ATV630, ATV650, ATV660, ATV680 and APM drives

Environment:
All

Cause:
N/A

Resolution:
To connect to the embedded web page on the ATV6xx drive, you must first enter an IP address in the drive.  You may also need to enter a Subnet Mask and Gateway address per the network requirements.  Then power cycle the drive.
Connect via an ethernet cable from PC to drive. Open your web browser, then type the drives IP address in your browser. On the log in page if you have version 1.4 or lower, the ID & password are both admin. If your drive is V1.5 or higher, the ID is admin, and the password is found under Menu 8.7 in the drive.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings