Sök bland vanliga frågor (FAQ)
Where can we find the Type-2 coordination chart for ATS22?
Type 2 coordination is not possible with ATS22 due to the soft starter internal design of power semiconductor & its internal by-pass . Only table for coordination type 1 is available in the catalog. Attached pdf pages for type 1 coordination .
Publicerad för:Schneider Electric Sverige
Bilagor
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj