{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.
Hur kan vi hjälpa dig idag?
Explain the digital input characteristics of PM3255 ?
The power meter can accept 2 digital inputs designated as DI1 and DI2.

The digital inputs have 4 operating modes:
• Normal Input Status: use for simple ON/OFF digital inputs. The digital inputs can be
OF or SD signals of a circuit breaker.
• Multi-tariff Control: you can control the tariff either through communications, the
internal clock or by 1 or 2 tariff inputs. Tariff control through the tariff inputs is
performed by applying a proper combination of ON or OFF signal to the inputs. Each
combination of ON or OFF signal results in the power meter registering the energy in
a particular tariff register. Refer to the table below for input coding.
• Input Metering: you can configure the meter in input metering modes to collect the
pulses for WAGES application. To activate this function, set the input metering pulse
frequency (pulse/unit). The meter counts the number of pulses and calculates the
number of units. Pulse width or pulse stop less than 10 milliseconds is invalid for
pulse counting.
• Energy Reset: energy reset function resets partial energy, energy by tariff, and
energy by phase. Reset is activated by an ON signal lasting for over 10 milliseconds.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Artiklar som kan vara till nytta
Utforska mer
Produktfamilj