Video: Sites/Devices cannot be connected in Power Monitoring Expert
Issue
Some sites and or devices cannot connect in PME. The IP addresses are unable to be pinged as well, but Modbus Tester or ION Setup can communicate successfully.
Product Line
PME7.x
PME8.x
PME 9.0, PME2020, PME2021, PME2022, PME2023
Environment
Device / site communications
Cause
Customers may block the Ping command through the network for security reasons. If Ping is blocked, and 'ICMP Timeout' is configured (in Advanced Properties of Site or Device configuration), this will cause them to not connect.
Resolution
Open the Advanced Properties section of the site or device by right clicking in the white space and change the 'ICMP Timeout' setting to 0, which is also the default value.
Some sites and or devices cannot connect in PME. The IP addresses are unable to be pinged as well, but Modbus Tester or ION Setup can communicate successfully.
Product Line
PME7.x
PME8.x
PME 9.0, PME2020, PME2021, PME2022, PME2023
Environment
Device / site communications
Cause
Customers may block the Ping command through the network for security reasons. If Ping is blocked, and 'ICMP Timeout' is configured (in Advanced Properties of Site or Device configuration), this will cause them to not connect.
Resolution
Open the Advanced Properties section of the site or device by right clicking in the white space and change the 'ICMP Timeout' setting to 0, which is also the default value.
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.