Power Meter Communication issue: Registers not reading the correct value.
Issue:
End user reads a modbus register and is getting a value other than what is expected

Product:
PowerLogic and ION meters

Environment:
Modbus Registers

Cause:
The Power meters, based on the manufacturing location, may have an offset.

In some meters the registers start from Zero and others may start from 1. So, the published register list varies accordingly.

Example: If Register 2017 is for Frequency of the meters it will read 60HZ.
But for the meter with offset the Register 2016 will read 60HZ.

Resolution:
Check the Modbus Register List for the specific meter you are trying to read for any indication that the registers have an offset. If it does you will need to shift the register by that offset to read the correct register.


Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

  • Produktväljare

    Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

  • Begär en offert

    Ställ din fråga online så kontaktar vi dig.

  • Här köper du

    Hitta enkelt närmaste Schneider Electric-distributör på din ort.

  • Hjälpcenter

    Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings