{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

Power Monitoring Expert (PME) Real time tables and Trends do not load data

Issue
Real Time Tables and Trends web application fail to display any real time data. Historical data can be displaced in the trends. Diagrams and Vista are able to display real time data.

Product
Power Monitoring Expert 7.2.x, 8.x, 9.0, 2020, 2021, 2022

Environment
PME supported browsers
Windows Firewall

Cause
PME uses undocumented port to connect to the Realtime Data Service

Resolution
Allow connections on TCP Port 23102 in the windows Firewall. To test if Windows Firewall is causing the issue user can stop the Windows Firewall Service and verify that data is being accessed via the web applications.

Note this port is included in later versions of the PME system guide.

Schneider Electric Sverige

Utforska mer
Produktfamilj
EcoStruxure™ Power Monitoring Expert Healthcare EditionEcoStruxure™ Power Monitoring Expert Data Center EditionEcoStruxure™ Power Monitoring Expert 8.2EcoStruxure™ Power Monitoring Expert Building Edition
Utforska mer
Produktfamilj
EcoStruxure™ Power Monitoring Expert Healthcare EditionEcoStruxure™ Power Monitoring Expert Data Center EditionEcoStruxure™ Power Monitoring Expert 8.2EcoStruxure™ Power Monitoring Expert Building Edition