Hur kan vi hjälpa dig idag?
140EHC10500 stops counting after the RIO cable is disconnected.
Issue
The 140EHC10500 stops counting when the RIO cable is disconnected.
Product Line
Quantum 140EHC10500 High speed Counter module.
Environment
Windows 10, ProWORX 32, Unity
Issue
If you disconnect the RIO cable from the Remote IO drop that contains an 140EHC10500 High Speed Counter module,
the module stops counting.
This works as designed. If the CPU loses communications with the 140EHC10500, it is designed to stop counting.
when this happens, the outputs will be set the to the selected output behavior.
When the RIO cable is plugged back, the module will need to be restarted. For additional information, reference page 30 and 69 in the attached user manual.
The 140EHC10500 stops counting when the RIO cable is disconnected.
Product Line
Quantum 140EHC10500 High speed Counter module.
Environment
Windows 10, ProWORX 32, Unity
Issue
If you disconnect the RIO cable from the Remote IO drop that contains an 140EHC10500 High Speed Counter module,
the module stops counting.
This works as designed. If the CPU loses communications with the 140EHC10500, it is designed to stop counting.
when this happens, the outputs will be set the to the selected output behavior.
When the RIO cable is plugged back, the module will need to be restarted. For additional information, reference page 30 and 69 in the attached user manual.
Publicerad för: Schneider Electric Sverige
Bilagor
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.