What can cause a CANopen CoF fault on the ATV320 drive?

Issue:
ATV320 CANopen CoF fault

Product Line:
Altivar ATV320

Environment:
All

Cause:
Communication interruption on the CANopen® bus.

Resolution:
• Check the CANopen cables on the communication bus, check to see if there are 120 ohm line terminator resistors installed, check and verify baud rate setting parameter BDCO.
• Refer to the CANopen® User's manual: https://www.schneider-electric.com/en/download/document/NVE41309/

Module LED color & status description
-OFF No detected error reported Red single flash Detected error reported by the CANopen controller of the Altivar 320 (example: too many detected error frames)
-Red double flash Detected error due to the occurrence of a Node Guarding or a Heartbeat event
-Red ON The CANopen controller is in Bus OFF state

Schneider Electric Sverige

Bilagor
ATV320_CANopen_Manual_EN_NVE41309_02.pdf [1.38 MB]
Utforska mer
Produktfamilj
Kategori:
Utforska mer
Produktfamilj
Kategori:

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings