Issue:
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.