Can a logic input be assigned to the external fault in ATV320 drive?
Issue:
How can I configure an external fault using logic input in ATV320 drive?
Product Line:
ATV320 drive
Environment:
All Serial numbers
Cause:
Application requires an external fault via a logic input.
Resolution:
Yes, a logic input can be assigned to a external fault.
External Fault can be accessed: DRI- > CONF > FULL > FLT- > EtF- > EtF
Then assign (LI1) to (LI6), logic input that is not assigned to any other functions.
Logic can be configured (LEt) As LO [Active low] (LO) or HIG [Active high] (HIG)(default).
It defines the positive or negative logic of the input assigned to the detected fault.
Configure EPL [External fault mgt] for Type of stop in the event of an external fault.
How can I configure an external fault using logic input in ATV320 drive?
Product Line:
ATV320 drive
Environment:
All Serial numbers
Cause:
Application requires an external fault via a logic input.
Resolution:
Yes, a logic input can be assigned to a external fault.
External Fault can be accessed: DRI- > CONF > FULL > FLT- > EtF- > EtF
Then assign (LI1) to (LI6), logic input that is not assigned to any other functions.
Logic can be configured (LEt) As LO [Active low] (LO) or HIG [Active high] (HIG)(default).
It defines the positive or negative logic of the input assigned to the detected fault.
Configure EPL [External fault mgt] for Type of stop in the event of an external fault.
Publicerad för: Schneider Electric Sverige


Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.