What is the Low Battery Duration setting used for?
Issue:
What is the network card low battery duration setting used for?
Product:
Network Management Card
PowerChute Network Shutdown
Environment:
AP9617, AP9618, AP9619, AP9630, AP9631, AP9635, AP9640, AP9641
Cause:
Informational
Solution:
Low Battery Duration is an alarm that will trigger shutdown when the UPS runtime remaining falls below the set time.For example, if the Low Battery Duration is set to ten minutes, and the UPS predicted runtime remaining reaches ten minutes or below, a low battery condition is triggered. When the alarm is triggered, the network card will send a signal to each configured PowerChute client, and the clients will begin the shutdown process. If input power is not restored to the UPS, it will turn off when the battery has exhausted.
PowerChute considers the low battery alarm to be a critical event. It is not configurable within the PowerChute GUI. It is recommended that the Low Battery Duration is configured to allow enough time for the PowerChute client's OS shutdown to complete.
For assistance with Low Battery Duration and Available Runtime has been Exceeded alarm in PowerChute Network Shutdown, see Schneider Electric PowerChute Network Shutdown reports "Available runtime has been exceeded".
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.