How to set PID preset references for the ATV630 drive?
Issue:
Can I program drive to switch between different set points on PID controller for the ATV630 drive?
Product Line:
ATV630
Environment:
All models, all serial numbers
Cause:
Customer wanted to easily switch between three set points, 40, 60 and 80 PSI.
Resolution:
Under the main menu, enter complete setting -> Pump Functions -> PID Controller -> PID Reference -> PID preset references:
Assign a digital input (DI5) for 2 PID Preset Assign
Enter 40PSI for RefPID Preset 2
Assign a digital input (DI6) for 4 PID Preset Assign
Enter 60PSI for RefPID Preset 3
Enter 80PSI for RefPID Preset 4
Note: This function can be accessed if [PID feedback ass.] PIF is assigned.
Can I program drive to switch between different set points on PID controller for the ATV630 drive?
Product Line:
ATV630
Environment:
All models, all serial numbers
Cause:
Customer wanted to easily switch between three set points, 40, 60 and 80 PSI.
Resolution:
Under the main menu, enter complete setting -> Pump Functions -> PID Controller -> PID Reference -> PID preset references:
Assign a digital input (DI5) for 2 PID Preset Assign
Enter 40PSI for RefPID Preset 2
Assign a digital input (DI6) for 4 PID Preset Assign
Enter 60PSI for RefPID Preset 3
Enter 80PSI for RefPID Preset 4
Note: This function can be accessed if [PID feedback ass.] PIF is assigned.
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.