How is calculated the processor load value in the BMXNOC0401 communication module?
Issue:
How is calculated the Processor load value in the BMXNOC0401 communication module?
Product Line:
M340
BMXNOC0401
Environment:
Web page
Resolution:
Processor load value is a ratio between “CPU non-Idle tasks Time” and “Total CPU time”( if idle is 30% then CPU utilization is 100-30=70%).
The CPU is a multi-task system, the execution order of the different type of tasks depend on their priorities .
In the case of the BMXNOC0401, the following tasks have an impact on its load :
How is calculated the Processor load value in the BMXNOC0401 communication module?
Product Line:
M340
BMXNOC0401
Environment:
Web page
Resolution:
Processor load value is a ratio between “CPU non-Idle tasks Time” and “Total CPU time”( if idle is 30% then CPU utilization is 100-30=70%).
The CPU is a multi-task system, the execution order of the different type of tasks depend on their priorities .
In the case of the BMXNOC0401, the following tasks have an impact on its load :
- Server and client traffic packets per second as each packet is inspected and a transaction occurs
- Size of I/O scanner image: bigger the scanner load, the longer it takes to copy from the xbus
- PLC CPU scan time, as we have to transfer the I/O scanner twice a scan cycle.
- General network traffic like multicast and broadcast traffic as it must be inspected
Publicerad för: Schneider Electric Sverige
Utforska mer
Produkt:
Produktfamilj
Utforska mer
Produkt:
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.