Why the BMXAMI0810 only reports MOD_ERROR in the IODDT?
Why the BMXAMI0810 only reports MOD_ERROR in the IODDT T_GEN_MOD?
N/A When any channel comes across brokenWire,upperOvr,lowerOv,spiError,or HARDWARE_SELF_TEST_FAULT, the MOD_ERROR will be activated. In special when the channel
has problems, the CH_ERROR will be activated also.
If there is only MOD_ERROR in the IODDT, customer has to verify the upper overflow or lower overflow.