{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

Getting premature schedule manufacturer maintenance alarm on Masterpact MTZ Micrologic X control unit

Issue:
Why am I getting a scheduled maintenance alarm when  the breaker is brand new and recently placed into service?
Sched. Manufact. maintenance within 3 months  Id: 0x1482

Product Line: Circuit Breakers

Environment: Masterpact MTZ with Micrologic X  control unit

Resolution:
The commissioning date within the control unit may have been left blank.  Use EcoStruxure Power Commision (EPC) commissioning software to correctly fill in the commissioning date.  See attached screen shot, to locate commissioning date in EPC.

Schneider Electric Sverige

Bilagor

Commissioning Date in EPC.jpgCommissioning Date in EPC.jpg [27.21 KB]
MTZ Schedule manufacturer maintenance within 3 months on display Id 0x1482.JPG.jpgMTZ Schedule manufacturer maintenance within 3 months on display Id 0x1482.JPG.jpg [61.76 KB]
Utforska mer
Produktfamilj
MasterPact MTZ Circuit Breakers - UL/ANSI
Utforska mer
Produktfamilj
MasterPact MTZ Circuit Breakers - UL/ANSI